EFFICIENT HEATING OF SANITARY WATER WITH HEAT PUMP
CALENTAMIENTO EFICIENTE DE AGUA SANITARIA POR BOMBA DE CALOR
Luis Juanicó
Universidad Nacional del Comahue. Instituto Andino Patagónico de
Tecnologías Biológicas y Geoambientales, CCT Patagonia Norte - CONYCET.
Argentina.
luisjuanico1966@gmail.com
https://orcid.org/0000-0003-2422-647X
Italo Carlos Bove Vanzulli
Universidad de la República (Udelar). Facultad de Ingeniería,
Laboratorio de Energía Solar. Uruguay.
italo@fing.edu.uy
https://orcid.org/0000-0001-8450-8183
Received: 28 / 05 / 2020 and Accepted: 04 /11 /2020
ENERLAC. Volume V. Number 1. June, 2021 (94 - 104)
ISSN: 2602-8042 (printed) / 2631-2522 (digital)
Foto de Alexander Schimmeck de Unsplash.
ABSTRACT
This work presents a thermal and economical assessment about replacing
the conventional household water heater with a heat pump water heater,
which efficiency is several times higher than the previous one. Thus,
the efficiency calculated for capitals of Latin American countries has
obtained average values ranging from 298% to 434%. However, the payback
period obtained is also related to the electricity tariff and the
temperature of the cold-water grid, which varies from 0.064 US$/kWh in
Paraguay to 0.233 US$/kWh in Costa Rica, and from 10 °C (La Paz) to
26.8 °C (Costa Rica). Thus, a ranking of payback period (replacing/ new
installation) was performed for average consumption of a five-person
family, obtaining values ranging from 2.4/1.4 years (Montevideo) to
10.5/6.1 years (Asunción), and also it was calculated the energy annual
saving obtaining from 1,436 kWh (Costa Rica) to 2,660 kWh (La Paz).
Consequently, we have found great potential for household energy saving
in Latin-American countries by substituting the conventional water
heater with a heat pump.
Keywords: Thermal Modeling, Household Electric Water Heaters, Heat Pump
for Water Heating, Energy Efficiency, Economic Analysis.
RESUMEN
Se presenta un análisis térmico-económico sobre la sustitución del
termotanque hogareño convencional por una bomba de calor, cuya
eficiencia es varias veces mayor. Así, la eficiencia promedio calculada
en las capitales de países latinoamericanos varía del 298% al 434%. Sin
embargo, y como será analizado, el período de repago obtenido depende
también de la tarifa eléctrica y de la temperatura del agua fría de
red, yendo desde 0.064 US$/kWh (Paraguay) hasta 0.233 US$/kWh (Costa
Rica), y desde 10 °C (La Paz) hasta 26.8 °C (Costa Rica). Para una
familia promedio de 5 personas se calculó un ranking (recambio/nuevo)
con períodos de repago que van de 2.4/1.4 años (Montevideo) a 10.5/6,1
años (Asunción); además, se calculó el ahorro anual de energía, desde
1,436 kWh (Costa Rica) hasta 2,660 kWh (La Paz). Así, hemos encontrado
un gran potencial de ahorro energético en los hogares de los países
latinoamericanos al sustituir el calentador de agua convencional por
una bomba de calor.
Palabras clave: Modelado Térmico, Calentadores Eléctricos de Agua;
Bomba de Calor; Calentamiento de Agua, Eficiencia Energética, Análisis
Económico.
INTRODUCTION
The energy consumption related to sanitary water heating demand (SWHD)
represents a major fraction (ranging from 30% to 75%) of total
households in warm or temperate climates, as it was pointed out by
several authors; for example, Iannelli y Pietro (2016), Sanders and
Webber (2015), Keinath and Garimella (2017), Vieira, Beal, and Stewart
(2014), Romero (2011), and Raimo (2010). Besides, since this
consumption (usually supplied by electrical heaters) is demanded at the
peak period (from 5 pm to 11 pm), it also impacts both, the generation
and the distribution electrical systems.
The water-storage electrical heater (WSEH) is the preferred appliance
in Latin American countries to provide the SWHD. This appliance heats
the water using an electrical resistance submerged into the water tank,
which is kept to a constant usable temperature (~45 °C) by the
thermostat and is thermally insulated to reduce this standby
consumption throughout the whole day. The power consumed by these
appliances is about 1,500 W, being this power noticeable lower than for
direct-current heaters or showers (that is, without tank), which is
about 5,500 W (as the well-known Brazilian shower). This advantage is
counterbalanced by the weakness of needing a long heating period when
the tank is filled with cold water, or otherwise, it has to waste a
stand-by consumption. This stand-by consumption could be enlarged due
to the need of keeping the water tank at higher temperatures (up to 75
°C) to extend its capacity (by mixing with cold water), for example,
when the dwellers have to take several showers continuously.
The authors have studied the WSEH in detail and developed some new
strategies, based on the hourly controlling of the thermostat, to
minimize its stand-by consumption (citations deleted A & B). They
also developed a numerical code useful for calculating its energetic
performance which will be summarized in the next section. Following
these previous works, this paper evaluates the energy-saving achievable
for a family by using a new kind of water heater, which is based on a
high-efficiency Heat Pump Water Heater (HPWH). Regarding that, the
performance of any heat pump is related to the ambient temperature, and
in this case, also to the grid-water temperature, we will analyze these
factors for the conditions of different Latin-American countries, which
vary from temperate to warm climates.
Although the heat pumps have been used in Sweden during last 30 years
for industrial applications that are still running (Averfalk et al.,
2014), this technology has been generalized for domestic water heating
just in the last ten years, as it was pointed out by Stafell, Brett,
Brandon and Hawkes (2012), Willem, Lin and Lekov (2017), Pardiñas,
Alonso, Diz, Husevåg and Fernández-Seara (2017) and Mengjie, Ning,
Yingji and Shiming (2019). This way, every year one million HPWH are
installed in Europe. Besides, this technology is continuously
improving, achieving efficiencies of up to 700% in some new prototypes
(Hua, Ge, and Wang, 2019).
The functioning of every heat pump is similar to any modern air
conditioning equipment (like a cooling/heating split air conditioning),
which (in its heating mode) takes heat at low temperature from the
outdoor ambient by the evaporator unit, and delivers it to the indoor
ambient by the condenser, after that the compressor increases the fluid
temperature. According to the type of fluid selected and the detailed
design of every component, this thermodynamical cycle can be designed
for operating from -25 °C (evaporator) to 65 °C (condenser), so that it
is very suitable for providing SWHD even in developed countries having
cold climates.
Up until today, two different kinds of HPWH are available in the
market, one is an integrated device, and the other is a split device.
The integrated design is suitable for indoor using, and so, it mounts a
small and quietly compressor above a big water tank (300 liters), to
satisfy a large hot water demand by using a low (375 W) heating power
([BCI for ACS in MLC], 2019). On the other hand, the split design used
the external unit (evaporator) of any standard air conditioning system
together with an indoor water tank that is heated by using a coiled
heat exchanger, instead of the condenser. These tanks (with a
copper-coiled heat exchanger and thermal insulations) are nowadays
manufactured massively in China (having capacities ranging from 100 to
5,000 liters) as much as the evaporator, and consequently, a split HPWH
is cheaper than the previous integrated design. For example, a split
HPWH (compressor power of 875 W, the tank of 150 liters) costs 1,200
dollars in Latin American countries (only 400 dollars in China),
meanwhile a less powerful (375 W) integrated HPWH costs 1,800 dollars.
([BCP for ACS in MLU], 2019; [BCP for ACS in MLC], 2019; [BCI for ACS
in MLC], 2019). However, to date, these types of equipment are almost
unknown in Latin American countries although they are based on the same
technology that any modern heat pump for air conditioning system, and
so, there are many technical services that could easily install them.
This technology is well established for cold developed countries, but,
precisely in the warm climates of Latin American countries is where it
would obtain better performances, due to several causes: 1) lower
temperature gradient for heating water from the water grid; 2) concerns
related to freezing on the evaporator on ambient temperatures below 4
°C are not frequent (Song, Deng, Dang, Mao and Wang, 2018); and 3) low
electrical tariffs, being noticeably lower than in European countries
(i.e., 0.6 US$/kWh Spain). In this work is studied the energetical and
economic performance of HPWH in Latin American countries regarding a
standard SWEH, for a 3-person and 5-person average family.
NUMERICAL MODEL
The thermal modeling of the standard Water-Storage Electrical Heater
(WSEH) was developed in previous works, (citations deleted A & B),
which is based on the energy conservation on the water tank. Thus,
considering a standard (Joule’s effect) electrical heater having
efficiencies about 100%, the electrical energy daily consumed (Ed) is
equal to the sensible heat required so that the hot water mass (M)
consumed can be heated from the water-grid cold temperature (Tc) to the
desired usable hot temperature (Th), plus the heat daily losses through
the thermal insulation of the tank, Ql:
Where Cp is the specific heat of water, and Ql is calculated as the
convective heat losses to the indoor ambient (for indoor tanks). Thus,
for a tank of external area (A) that is kept at a constant temperature
set by the thermostat (Tt), within an ambient temperature (Ta), and
having a uniform insulation layer of thermal transmittance K (W/m2/°C),
Ql can be calculated by:
From here, by considering a similar heat pump device (that is, having
the same tank volume, insulation quality, and thermostat working
temperature), this thermal model can be also applied, but taking into
account that now the efficiency is determined by the coefficient of
production (COP), which relates the heating power obtained and the
electrical power consumed, by:
The COP value on any heat pump depends on the temperature difference
(ΔT) between the outdoor ambient (the heat source) and the heated water
(the heat sink), which has been fitted by Staffell et al. (2012) by
using a quadratic function:
On the other hand, regarding that the energy consumed for heating water
is related to its starting (cold) temperature, it is relevant to take
into account the temperature of the tap-water grid. We have solved the
lack of available data on grid temperatures for each city studied here,
by using the general modeling developed by the National Laboratory of
Renewable Energies of USA (NREL; Hendron, 2006). In this model, the
temperature of the water grid follows the monthly average or the mean
ambient tempera-ture with an offset of +3.0 °C. We will estimate the
heat pump performance by considering only the annual mean temperatures
(for both, the ambient and the water grid), and so, neglecting the
seasonal variations of these variables. Let us note from eq. (4) that
the efficiency of the heat pump does not depend linearly on the
temperature difference, and so, our simplified model introduces a
seasonal error. However, we have verified that this assumption causes
an error lower than 3% in all the studied cases, and so, this
simplified methodology is reasonable.
RESULTS
The following assumptions have been used for all cases studied:
a) A constant indoor temperature, set to 20 °C. This is reasonable
regarding its modest effect, lower than 5 %, on the standby heat
losses.
b) The water tank has average-quality thermal insulation, made by a 5
cm-thickness layer of polyurethane foam, which provides a thermal
transmittance K = 0.6 W/m2/°C.
c) A standard cylindrical water tank (150 liters, 0.4 m diameter).
d) Average daily consumption of hot water for each person, which is
represented by 45 liters at 40°C (shower) and 10 liters at 50°C
(cleaning dishes and others), according to previous works (citations
deleted A & B).
e) Thermostat set to 50 °C; this level is enough for satisfying all the
household demands, but not causing overheating, which in turn would
lead to higher heat losses on the tank.
f) A constant outdoor ambient temperature and equals to its mean annual
value for every location studied.
g) The annual mean temperature of the water grid equals to the mean
ambient temperature plus 3.0 °C, according to the NREL model (Hendron,
2006).
Hence, based on these simplifications and by using the modeling
developed in the previous section, we obtain the results illustrated in
Table 1. Here is shown the annual average values of the ambient
temperature for fifteen major Latin American cities (CLIMATE-DATA.ORG,
2020), and the coefficient of performance (COP) that a HPWH would
obtain in these cities (in increasing order). Thus, it was obtained a
wide range of efficiencies, ranging from 298 % (La Paz) to 424 %
(Guayaquil). Besides, here is shown the annual energy consumption of
the heat pump for families of 3 or 5 persons; we see that this energy
consumption is lower as higher the COP is.
Table 1. Ambient temperatures and annual consumptions for using HPWH in
different cities
Source: Own elaboration, 2020
Table 2 presents the annual energy consumption of a conventional water
heater (WSEH) for the 3-person family (column #1) and the 5-person
family (column #2). Besides, taking into account the energy
consumptions by using the heat pump (calculated in table 1), table 2
presents the energy saving that could be achieved by installing a heat
pump water heater (HPWH), in columns #3 and #4, in increasing order.
This new ranking is almost opposite to the one performed in Table 1,
due to the energy consumption of the conventional heater increases
noticeably in cold climates, since the grid water must be heated much
more than in warm climates, and this effect cancels the lower
performance of heat pumps in cold climates. Therefore, it is observed
that the lower the ambient temperature is, the higher the energy-saving
obtained is, for substituting the conventional heater with a modern
heat pump.
Table 2. Annual energy consumption by using conventional WSEH and the
saving achievable by the new HPWH
Source: Own elaboration, 2020
Finally, in Table 3 is presented another ranking, which is related to
the payback period of the investment required for substituting a
conventional heater by a heat pump heater (costing US$ 1,200), or for
installing it in a new house (costing US$ 700 in this case, since the
WSEH could cost another US$ 500). In this ranking, the electrical
tariffs (OSINERGMIN, 2020) play a major role, and so, it is different
from both previous ones. Here, note that a longer payback period is
usually found for a lower electrical tariff, but not always, since the
energy-saving also depends on the ambient temperature. From these
results, we can conclude that although Guayaquil is the warmest city
studied (and so, where the heat pump gets the best performance), the
best economic performance is obtained in Montevideo. This result is due
to the combination of three factors:
1) Having moderate ambient temperature, the COP obtained is moderate
too (neither the best one nor the worst one);
2) According to its temperate climate, the energy consumption related
to heating water is noticeably increased, and so, we can obtain a
noticeable energy saving by substituting the conventional heater;
3) This electrical tariff is the highest one, and so, this noticeable
energy saving can be transferred into an outstanding economic
performance.
Table 3. Payback period obtained by installing the HPWH
Source: Own elaboration, 2020; Tariffs were obtained from OSINERGMIN,
4th semester 2018
Let us note that the payback period is the simplest merit figure used
on financial analysis to estimate the profitability of potential
investments (the number of periods required to mortgage the investment
is calculated through dividing the investment by the annual saving
obtained by using the modern HPWH instead of the WSEH), instead of, for
example, the internal return rate. However, the payback period is
suitable for this case considering both, the simplicity involved in
this analysis, and the fact that the national discount rate and the
evolution of the relative prices of energies sources are quite
different between Latin American countries studied.
CONCLUSIONS
This work studied a modern high-efficiency system of water heating
based on the thermodynamic cycle of the heat pump. These systems have
been used for a decade in developed countries intended for household
energy efficiency, although their cold climates are a major drawback,
regarding that the heat pump performance is proportional to the ambient
temperature. This way, for example, the efficiency achieved in Oslo (6
°C) is 270%, meanwhile in the warm Latin American climates can be
obtained efficiencies up to 424%. However, as we have demonstrated
here, the potential of saving achievable (by substituting the old
conventional heater for a modern heat pump heater) is larger as lower
the ambient temperature is. This unexpected result is caused by the
major effect related to the lower temperature of the water grid, which
in turn causes a higher energy consumption in the conventional heater,
and in turn, a larger saving by substituting it by the heat pump.
On the other hand, by performing an economic assessment about this
substitution, we have concluded that the residential tariff of
electricity also plays a major role, together with the previous ones.
These tariffs vary considerably in Latin American countries, ranging
from 55.5 US$/MWh (Paraguay) to 213 US$/MWh (Uruguay). Thus, for a
five-person average family, the short payback period for substituting
the old appliance was found in Montevideo (2.7 years), due to their
very high tariff and temperate climate. In opposition, the longest
payback period was found in Asunción (13.4 years), due to their low
tariff and although its warm climate.
The sum of all these factors previously analyzed is obtained by the
numerical tool developed here, which has proven to be useful for
evaluating different configurations and climatic conditions. For
example, the payback period also depends on the level of the household
demand (that varies with the number of persons, etc.), the temperature
of the thermostat (that defines the efficiency achieved by the heat
pump, together with the ambient temperature), and other minor
variables, such as the volume of the water tank and the thermal
insulation quality (that define the stand-by heat losses), which are
considered on this model.
Regarding the economic performance, if it is considered as reasonable
an investment that can be mortgaged in five years, the substitution of
the conventional heater by the heat pump is affordable in six cities
(Montevideo, Santiago, San José de Costa Rica, Lima, La Paz y Bogotá)
among a total of fifteen cities studied, for a five-person family.
However, we also can observe that this figure is reduced to only one
city for a three-person family, according to the very low capacity
factor of this equipment (running less than an hour per day). This poor
performance could partially explain the neglectable penetration of this
technology in Latin American markets. However, we can also be optimist
regarding the future, due to:
1) The competitiveness of the heat
pump increases when it is considered its application on new houses, in
which the investment required is lower (subtracting the cost of the
conventional heater). Thus, a good performance is obtained for 12 or
these 15 cities for a five-person family.
2) The local price of the HPWH is very high due to its negligible
volume of the Latin American local markets (and tax for importation),
but the international cost it just one third (US$ 400, FOB Hong Kong).
3) The competitiveness of the HPWH increases noticeably when it is
intensively used. For a fully using case (24x7), we could obtain
payback periods ranging from 2 to 11 months.
Upon these considerations, we could test now a proposal to Latin
American governments, promoting the fast penetration of this technology
for supply sanitary hot water demands. This proposal consists of
several executive orders:
1) To make tax-free all the
household HPWH, which is based on using renewable energy (let us note
that the heat pump uses the ambient heat that comes from the sun, and
so, it can be considered as a “solar” technology). Hence, we are
suggesting to take for HPWH the same considerations that often are
given to solar technologies (photovoltaic panels and thermal
collectors).
2) Driving the development of the local market by making several
large purchase orders, used to fulfill the demand of governmental
buildings (hospitals, etc.) that require a 24x7 demand.
3) Although it is true that one family household cannot represent
this case, a large building with a centralized supply of sanitary hot
water can certainly be one of these intensive applications.
4) The application of HPWH, although being almost unknown in this
region, does not imply any technical challenger, since is similar to
any split air conditioning device.
For these reasons, we believe that, regarding the fast-growing of
renewable low-scale technologies recently observed here, the Latin
American region is now mature for achieving a similar behavior on the
development of HPWH, which could certainly enhance the penetration of
solar technologies to many users that maybe are reluctant to install
some “estrange devices” over their roofs, or in other roofs where the
direct solar irradiation is blocked for neighbor buildings. For all
these cases, the HPWH could provide a new solution within the portfolio
of renewable energies.
REFERENCES
Averfalk, H., Ingvarsson, P., Persson, U., Gong, M. and Werner, S.
(2017). Large heat pumps in Swedish district heating systems. Renewable and Sustainable Energy Reviews 79, 1275-1284.
[BCI for ACS in MLC]. (2019). Mercado libre Chile: Bomba de calor sistema integrado para ACS.
Recuperado el 13/05/19.
https://articulo.mercadolibre.cl/MLC-435285201-termo
-agua-caliente-bomba-de-calor-300-lts-kaltemp-_JM? quantity=1
[BCP for ACS in MLC]. (2019). Mercado libre Chile: Bomba de calor sistema partido para ACS. Recuperado el 11/09/19. https://articulo.mercadolibre.cl/MLC-490459126-bomba-de-calor-para-aguas-sanitarias-_JM
[BCP for ACS in MLU]. (2019). Mercado libre Uruguay: Bomba de calor sistema partido para ACS.
Recuperado el 13/05/19. https://articulo.mercadolibre.com.uy/MLU-
449003949-termotanque-super-eficiente-por-bomba-de-calor--_JM?quantity=1
CLIMATE-DATA.ORG. (2020). Recuperado el 26/03/2020
Hendron, R. (2006). Building America research benchmark definition. Updated December 15, 2006. NREL/TP-550- 40968, Golden, CO: National Renewable Energy Laboratory.
Hua, L.J., Ge, T.S. and Wang, R.Z. (2019). Extremely high efficient heat pump with desiccant coated evaporator and condenser. Energy 170, 569-579.
Iannelli, L. y Prieto, R. (2016). Eficiencia en el calentamiento de
agua. Consumos pasivos en sistemas convencionales y solares híbridos. Petrotecnia, Agosto, 86-95.
Keinath, C.M. and Garimella, S. (2017). An energy and cost comparison of residential water heating technologies. Energy, 128, 626-633.
Mengjie, S., Ning, M., Yingji, X. and Shiming D. (2019). Challenges in,
and the development of, building energy-saving techniques, illustrated
with the example of an air source heat pump. Thermal Science and Engineering Progress, 10, 337-356.
OSINERGMIN. (2020). Tarifas eléctricas residenciales en Latino América, 4to Trimestre 2018. Recuperado el 26/05/20. https://observatorio.osinergmin.gob.pe/tarifas-electricas-residenciales-latinoamerica
Pardiñas, A. A., Alonso, M. J., Diz, R., Husevåg Kvalsvik, K. and
Fernández-Seara, J. (2017). State-of-the-art for the use of
phase-change materials in tanks coupled with heat pumps. Energy and Buildings, 140, 28-41.
Raimo, A. P. (2007). Aquecimento de água no setor residencial. Programa Interunidades de Pós-Graduación en Energía, USP.
Romero, N. P. (2011). Consumo de energía a nivel residencial en Chile y análisis de eficiencia energética en calefacción.
(Tesis de grado en Ingeniería Civil). Universidad de Chile.
http://repositorio.uchile.cl/tesis/uchile/2011/cf-romero_
nr/pdfAmont/cf-romero_nr.pdf
Sanders, K.T. and Webber, M.E. (2015). Evaluating the energy and CO2 emissions impacts of shifts in residential water heating in the United States. Energy, 81, 317-327.
Song, M., Deng, S., Dang, C., Mao, N. and Wang, Z. (2018). Review of
improvement for air source heat pump units during frosting and
defrosting. Applied Energy, 211, 1150-1170.
Staffell, I., Brett, D., Brandon, N. and Hawkes, A. (2012). A review of domestic heat pumps. Energy & Environmental Science, 5(11), 9291-9306.
Vieira, A.S., Beal, C.D. and Stewart, R.A. (2014). Residential water
heaters in Brisbane, Australia: Thinking beyond technology selection to
enhance energy efficiency and level of service. Energy and Buildings, 82, 222-236.
Willem, H., Lin Y. and Lekov, A. (2017). Review of energy efficiency
and system performance of residential heat pump water heaters. Energy and Buildings, 143, 191-201.